ATEX Cable Gland PF8041200E 1/2" NPT
EExeII IP66&IP68 BlackNylon oø7-12mm
|
|
Cable Gland Type PF - (Single Compression Nylon Gland)
Peppers “PF” type glands, certified Increased Safety Ex e are suitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Group II. They are manufactured from polyamide and provide a controlled pull resistant displacement seal on the cable outer sheath providing both Ex e & IP protection. The gland has been tested to IP66 & IP68 to 50 metres and is fully compliant with the Ex e standard with no reduced impact restriction. Available in black or blue, in a range of thread forms complete with an IP flat washer on metric entry threads.
Operating Temperature: | M16-M63: -35°C to +95°C ° |
| M12: -20°C to +80°C |
Materials: | Polyamide |
IP Rating: | IP66 & IP68 (50 metres - 30 minutes) |
Impact Resistance: | 7Nm |
Optional Accessories: | Nylon Locknut / IP Washers |
Options: | Colour: Black / Blue |
| Industrial Non-Ex version: Omit “E” from part number |
Gland Size | Entry Thread Size | Nominal Protrusion [L] | Cable Sealing Range | Thread Length [E] | Part Number |
16 | 3/8” NPT | 27.0 | 5.0 - 8.0 | 11 | PF8040800E |
20 | 1/2” NPT | 27.0 | 7.0 - 12.0 | 14 | PF8041200E |
25 | 3/4” NPT | 35.0 | 12.0 - 18.0 | 15 | PF8042000E |
32 | 1” NPT | 41.0 | 16.0 - 25.0 | 18 | PF8042800E |
Compliance Standard: EN 60079-0, EN 60079-7, EN 61241-0, EN 61241-1
IEC 60079-0, IEC 60079-7, IEC 61241-0, IEC 61241-1 & IEC 60529
Certification:
ATEX: II 2 GD Ex e II / Ex tD A21
IECEx: Ex e II / Ex tD A21
GOST-R: Ex e IIU
UL: ANSI/UL514B
CSA: CAN/CSA C22.2
VDE: DIN EN 50262 / VDE 0619
LLOYD’S: Enclosure Systems (Part 1B)
Certificate No.:
ATEX: LCIE 07ATEX6082X/02
IECEx: LCI 10.0008X
GOST: POCC FR M14.B00153
UL: E306665
CSA: E306665
VDE: 131210
LLOYD’S: 10/00056
Notes:
* The user should seek expert advice if intending to combine flammable and combustible dust in one environment/installation.
* Assembly instructions must be read prior to installation and adhered to in full.
* If used in a threaded entry, NPT versions may protrude more than “L” length due to engagement of tapered threads.
* Industrial Non-Ex versions are not supplied with IP thread sealing washer.
* Industrial Non-Ex versions are only available in Black.